Our business promises all users of the first-class items and the most satisfying post-sale company. We warmly welcome our regular and new prospects to join us for 40 Amp Rcbo, Mcb Busbar Link, Rcd Consumer Unit, Winning customers' trust is definitely the gold key to our good results! If you are fascinated in our products, make sure you sense absolutely free to go to our web site or make contact with us.
OEM Ac Mcb Switch Factory – 1P, 2P, 3P, 4P B C D curve, MCB, ETM10, AC, miniature circuit breaker, mini circuit breaker, din rail – Etechin Detail:

Products Description

ETM10 series MCB is in complied with IEC 60898-1 standard. It has the certification of Semko, CE and CB
ETM10 have 4.5 6 kilo ampere for breaking capacity.
ETM10 have already gotten the Semko CE CB certification.
Our MCBs rated current is from 1 ampere to 63 ampere and it has one pole to four poles with b,c,d curve.
Rated insulation voltage: 230V, 240V, 230 / 240V (1 Pole); 400 / 415V (2 poles, 3 poles)
As we know MCB’s main functions is for overload protection and the short circuit protection the overload protection is mainly operated by bi-metal assembly parts, while the short circuit protection is meaning operated by coil assembly parts. As i mentioned before our MCB have b,c,d curve. Here are different usage between b, c, d curve. B and C curve are mainly for home use, while d curve is mainly for industry.
The indicator of MCB, it is for on and off function display. Red is on and green is off. From the MCB hole you will see our terminal screw which is with high torque 3 newton while IEC standard is required 2 newton.
The arc chamber of this MCB we have 11 plates for MCB 6ka design, and normal on the market the arc chamber only have 9 plates for 6ka. Our design is quick and efficient arc quenching and very low let’s through energy clustering.
It’s mounting type is to be mounted on din rail EN60715 35mm.

Technical Characteristic

Standard

IEC/EN 60898-1

Electrical

Rated current in

A

( 1 2 3 4) 6 10 16 20 25 32 40 50 63

features

Poles

1P 2P 3P 4P

Rated voltage Ue

V

230/400,240/415

Insulation coltage Ui

V

500

Rated frequency

Hz

50/60Hz

Rated breaking capacity

A

4.5/6KA

Rated impulse withstand voltage (1.2/50)Uipm

V

6000

Dielectric test voltage at and ind.Freq.for 1min

KV

2

Pollution degree

2

Themo-magnetic release characteristic

B C D

Mechanical

Electrical life

above 4000

features

Machanical life

above 10000

Contact position indicator

Yes

Protection degree

IP 20

Reference temperature of setting of thermal element

°C

30 or 50

Ambient temperature(with daily average≤35°C)

°C

-25~+55

Storage temperature

°C

-25…+70

Installation

Terminal connection type

Cable/Pin-type busbar

Terminal size top/bottom for cable

mm²

25

AWG

18-3

Terminal size top/bottom for busbar

mm²

25

AWG

18-3

Tightening torque

N*m

3.0

In-lbs.

22

Mounting

OnDIN rail FN 60715(35mm)

by means of fast clip device

Connection

From top and bottom

In civil building design, low-voltage circuit breakers are mainly used for line overload, short-circuit, over-current, voltage loss, under-voltage, grounding, leakage, automatic switching of dual power sources, and protection and operation of motors during infrequent starting. Principles In addition to complying with basic principles such as the use environment characteristics of low-voltage electrical equipment (see Industrial and Civil Power Distribution Design Manual), the following conditions should be considered: 1) The rated voltage of the circuit breaker should not be less than the rated voltage of the line; 2) The rated current of the circuit breaker and the rated current of the overcurrent release are not less than the calculated current of the line; 3) The rated short-circuit breaking capacity of the circuit breaker is not less than the maximum short-circuit current in the line; 4) The selection of power distribution circuit breakers needs to consider the short-time delay short-circuit on-off capability and the coordination between delay protection levels; 5) The rated voltage of the undervoltage release of the circuit breaker is equal to the rated voltage of the line; 6) When used for motor protection, the selection of circuit breaker should consider the starting current of the motor and make it inactive within the starting time; see “Industrial and Civil Power Distribution Design Manual” for design calculations; 7) The selection of circuit breakers should also consider the selective coordination of circuit breakers and circuit breakers, circuit breakers and fuses.


Product detail pictures:

OEM Ac Mcb Switch Factory –  1P, 2P, 3P, 4P B C D curve, MCB, ETM10, AC, miniature circuit breaker, mini circuit breaker, din rail – Etechin detail pictures

OEM Ac Mcb Switch Factory –  1P, 2P, 3P, 4P B C D curve, MCB, ETM10, AC, miniature circuit breaker, mini circuit breaker, din rail – Etechin detail pictures

OEM Ac Mcb Switch Factory –  1P, 2P, 3P, 4P B C D curve, MCB, ETM10, AC, miniature circuit breaker, mini circuit breaker, din rail – Etechin detail pictures

OEM Ac Mcb Switch Factory –  1P, 2P, 3P, 4P B C D curve, MCB, ETM10, AC, miniature circuit breaker, mini circuit breaker, din rail – Etechin detail pictures

OEM Ac Mcb Switch Factory –  1P, 2P, 3P, 4P B C D curve, MCB, ETM10, AC, miniature circuit breaker, mini circuit breaker, din rail – Etechin detail pictures

OEM Ac Mcb Switch Factory –  1P, 2P, 3P, 4P B C D curve, MCB, ETM10, AC, miniature circuit breaker, mini circuit breaker, din rail – Etechin detail pictures

OEM Ac Mcb Switch Factory –  1P, 2P, 3P, 4P B C D curve, MCB, ETM10, AC, miniature circuit breaker, mini circuit breaker, din rail – Etechin detail pictures

OEM Ac Mcb Switch Factory –  1P, 2P, 3P, 4P B C D curve, MCB, ETM10, AC, miniature circuit breaker, mini circuit breaker, din rail – Etechin detail pictures


Related Product Guide:

The incredibly abundant projects administration experiences and 1 to one provider model make the superior importance of small business communication and our easy understanding of your expectations for OEM Ac Mcb Switch Factory – 1P, 2P, 3P, 4P B C D curve, MCB, ETM10, AC, miniature circuit breaker, mini circuit breaker, din rail – Etechin , The product will supply to all over the world, such as: Montpellier, United Arab Emirates, Australia, They're durable modeling and promoting effectively all over the world. Under no circumstances disappearing major functions in a quick time, it's a should for you of excellent good quality. Guided by the principle of "Prudence, Efficiency, Union and Innovation. the company make a terrific efforts to expand its international trade, raise its company profit and raise its export scale. We're confident that we are going to possess a vibrant prospect and to be distributed all over the world within the years to come.
  • This company conforms to the market requirement and joins in the market competition by its high quality product, this is an enterprise that have Chinese spirit.
    5 Stars By Abigail from United Kingdom - 2017.05.21 12:31
    Product variety is complete, good quality and inexpensive, the delivery is fast and transport is security, very good, we are happy to cooperate with a reputable company!
    5 Stars By Susan from Italy - 2017.08.18 18:38
    Write your message here and send it to us